Brand Name : Coolmay
Model Number : QM3G-70FH-24MR-2AD-V-485P
Certification : CE
Place of Origin : Shenzhen
MOQ : 1 pcs
Price : Negotiable
Payment Terms : T/T, Western Union, MoneyGram
Supply Ability : 100,000 pcs per month
Delivery Time : 3-7 work days
Packaging Details : Packed with standard carton box
Cutout size : 192*138mm
Dimension : 200*146*36mm
DI/DO : Max 24DI/20DO (max 16MR)
Analog I/O : (optional) Max 12AI/8AO
HMI COM port : Type-C HMI download port
PLC COM port : RS485
Advantage:
◆ Upper computer programming software compatible with Works 2/GX Developer8.86 (supports Ladder diagram and SFC language, does not support structured programming/labels).
◆ Powerful, compatible with FX3G/FX3U/FX3S PLC, high processing speed.
◆ Military level 32 bit CPU adopted, which is faster and more adapted to industrial environment of high electromagnetic interference.
◆ Flexible use. More specifications and batches can be customized according to customer requirements.
◆ 32K program capacity, 32K retentive register, support interrupt, linear arc interpolation ,PID auto-tuning, high powerful.
◆ The PLC is compatible with Mitsubishi programming software, and the HMI uses TK series human-machine interface programming software mView.
Parameter:
Display | Dimension | 200*146*36mm |
Cutout size | 192*138mm | |
Type | 7"TFT | |
Feature | 60K-color resistive touch screen, supports portrait display | |
Memory | RAM | 64MB |
ROM | NOR Flash 16MB | |
CPU | 32bit CPU 408MHz | |
I/O | DI/DO | Max 24DI/20DO (max 16MR) |
DI/DO level | Input: Passive NPN, public terminal isolated Transistor output: Low level NPN, COM connect to negative; Relay output: Normally open dry contact | |
DO type and load | Relay MR/MOS tube, MOS tube: 2A/point, 4A/4 point COM, 5A/12 point COM; MR: 2A/point, 5A/12 point COM. | |
Analog I/O (optional) | Max 12AI/8AO | |
AI type (optional) | Thermocouple E/E_/K/K_/S/S_/T/T_/J/J_ / PT100/ PT1000/ NTC10K/ NTC50K/ NTC100K/ 0~10V/ 0~5V/ 0~20mA/ 4~20mA/ -5V~5V/ -10V~10V / mixed | |
AO type (optional) | 0~10V /0~5V/ 0~20mA/ 4~20mA/ mixed/ -5~5V/ -10~10V (2AO for 1 minus voltage) | |
High-speed function | High-speed counting | Single phase 6 channel 60KHz, or 2 AB 60KHz + 1 AB 10KHz, or 2 ABZ 60KHz + 1 AB phase 10 KHz |
High-speed pulse | 8 channels, Y0-Y3 is 100KHz, Y4-Y7 is 10KHz. High-speed counting + high-speed pulse < 480KHz | |
Connection | HMI | Type-C HMI download port (can download PLC program through the USB penetrating function), RS232 port |
1 RS485 (changed from default RS232) | ||
PLC | 1 TYPE-C, 1 RS232 (program port) | |
1 RS485 or 2 RS485 COM ports (RS485 port on HMI and RS232 on PLC will be unavailable) | ||
CAN (2.0A/B) port, Ethernet port, WIFI (will occupy default RS232 port) | ||
Software | HMI | Coolmay mView HMI Programming Software |
PLC | Compatible with Mitsubishi GX Developer 8.86 and WORKS 2 |
Sampling of analog input:
Number of filter cycles=(R23600~R23615)*PLC scan time, if R23600=1, one PLC scan cycle will sample once, and the value in the first channel analog input will be changed once. The larger the value of R23600~R23615 is set, the more stable the result is.
R23600~R23615 are the number of filtering cycles, the default is 100 (range 2~20000), the data cannot be less than or equal to 0;
D8073 is the smoothing filter coefficient of all analog inputs, the setting range is 0~999.
RS485 20DO HMI PLC All In One Passive NPN HMI PLC Panel Images |